I Lightning rod protection
II Mesh cage protection
III Early streamer emission protection

I Lightning rod protection
Protection level : II as defined in NF C 17-102
Description of the installation that would have to be implemented : 6m high lightning rods installed on the roof to protect the stands and the court. On the roof: equipotential interconnections between the lightning rods. Each lightning rod is connected to a down conductor fitted with a dedicated earth rod.
Remarks : The tennis court design is such that lightning rods are not able to provide complete protection of the structure in compliance with the standard. This solution must be rejected.

II Mesh cage protection
Protection level : II as defined in NF C 17-102
Description of the installation that would have to be implemented : 50 cm capture points installed around the roof perimeter every 15 metres. 10 metre roof mesh grid. On the walls: down conductors every 15 metres, the bottoms of which are connected to a series of dedicated earth rods.
Remarks : The tennis court design is such that a mesh cage lightning conductor is not able to provide complete protection of the structure in compliance with the standard. This solution must be rejected.
III Early streamer emission protection
Protection level : II as defined in NF C 17-102
Description : 5m high early streamer emission lightning conductors installed on the roof. Protection radius Rp =97 metres (Δt = 60μs) for level II protection. Each lightning conductor is connected to a down conductor fitted with a dedicated earth rod.

Installation schematic :